PM error codes
Error code
(hex)
0001
0006
0007
0008
0011
5101
510C
5112
Note
The following applies for PM4000 DI/DO:
The error codes for short-circuit and wire break are each signaled for one group of 4
channels only. The number of the first channel of the group of 4 is entered as the channel
number.
Causes of error and remedies
You will find information about possible causes of error and remedies in Section Fault
reporting through diagnostics data (Page 101).
Note
If a fault status changes on a channel, the first fault to be reported is retained.
SIPLUS HCS4300
Operating Instructions, 11/2015, A5E35452705A/002
Description
Short-circuit
Wire break
Measurement range / upper limit
exceeded
Measurement range / lower limit
violated
No supply voltage
Communication error on HCS bus
Undefined error
Polarity reversal at measuring input
10.3 Transfer of diagnostic alarms to the controller
PM temperature
-
-
Communications
PM DI/DO
PM U/I
-
-
.
-
-
-
-
-
-
-
97