11.2.2

Fault reporting through diagnostics data

The device-internal monitoring functions recognize specific faults in the power output
module. The corresponding information is provided in the diagnostics data.
Causes of error and possible remedies
Error code
5104
5105
5106
5107
5109
510B
510E
SIPLUS HCS4300
Operating Instructions, 11/2015, A5E35452705A/002
Process and system messages, error handling
Description
Channel fault: Triac break-
down
"Breakdown" means the triac
is defective and conducts
continuously even without
being activated.
This fault can only be detect-
ed if the power output is
switched off. For a 100%
setpoint, the fault can be
neither detected nor indicat-
ed.
Channel fault: Fuse tripped or
triac has high resistance
Incoming fuse has tripped
Channel fault: Heating ele-
ment / emitter cable defective
Switch-off threshold for inter-
nal device temperature
At least one voltage is not
connected
Rotating field fault
11.2 Power Output Module (POM)
Possible causes / Corrective action
Triac is defective ⇒ Return POM
Switch off machine, check outgoing
fuse/cabling/heating element and rectify
fault, restart
Triac is defective => Return POM
Switch off machine, check return
fuse/cabling/heating element and rectify
fault, restart
Switch off machine, check ca-
bling/heating element and rectify fault,
restart
Trip threshold overshot: The heating is
switched off automatically by the device.
Actions:
Check the fan module is functioning
correctly (if installed)
Switch off the machine, rectify the fault
(e.g. cooling malfunction), restart
Check power supply / cabling and, if
necessary, connect the missing voltage
Check power supply / cabling and, if
necessary, connect the missing voltage