Installing/mounting
5.2 Installing the Power Output Module (POM)
5.2
Installing the Power Output Module (POM)
5.2.1
Busbar mounting
5.2.1.1
Preparations
Busbar system
The mains infeed for the power output module is connected via a 3-phase busbar system.
Suitable for the following busbar systems, for example:
● Siemens (SENTRON 60 mm)
● Wöhner (60 mm-EQUES)
Dangerous voltages on the busbar system
May cause death, serious injury or damage to property
Dangerous voltages can be present on the busbar system.
The busbar system must therefore be isolated and secured against reclosing before work
begins for mounting and connecting the HCS4300 heating control system.
NOTICE
Clockwise rotating field
When connecting the busbar system, make sure that the energy system is connected
clockwise.
Note
Residual current protective device
If a residual current protective device is provided for the busbar system, a protection device
of Type A is sufficient for the HCS4300.
34
WARNING
Operating Instructions, 11/2015, A5E35452705A/002
SIPLUS HCS4300