Siemens SIPLUS HCS Operating Instructions Manual page 93

Hide thumbs Also See for SIPLUS HCS:
Table of Contents

Advertisement

Dataset 202 "Measured values for PM4000 U/I"
Byte
0,1
2,3
4,5
6,7
8,9
10,11
12,13
14,15
16,17
18,19
20,21
22,23
24,25
26,27
28,29
30,31
The definition is by means of a structure with elements of type "INT".
The dataset is answered with errors if no PM U/I is present.
SIPLUS HCS4300
Operating Instructions, 11/2015, A5E35452705A/002
Description
Frequency (with one decimal place)
Measured voltage value L1/L12 (in [V] with one decimal place)
Measured voltage value L2/L23 (in [V] with one decimal place)
Measured voltage value L3/L31 (in [V] with one decimal place)
Measured current value RMS L1/L12 (in [A] with three decimal places)
Measured current value RMS L2/L23 (in [A] with three decimal places)
Measured current value RMS L3/L31 (in [A] with three decimal places)
Measured current mean value RMS L1/L12 (in [A] with three decimal places)
Measured current mean value RMS L2/L23 (in [A] with three decimal places)
Measured current mean value RMS L3/L31 (in [A] with three decimal places)
Power RMS L1/L12 (in [W] with one decimal place)
Power RMS L2/L23 (in [W] with one decimal place)
Power RMS L3/L31 (in [W] with one decimal place)
Power mean value L1/L12 (in [W] with one decimal place)
Power mean value L2/L23 (in [W] with one decimal place)
Power mean value L3/L31 (in [W] with one decimal place)
Communications
10.2 Acyclic data exchange
93