Analog Output X: Assignment Of The Lower Limit - Bosch Rexroth WGM Operating Instructions Manual

Oil humidity sensor
Table of Contents

Advertisement

28/46
Operation
Bosch Rexroth AG, RE 51550-B/09.2019
Temperature
Assignment of the temperature level where the maximum analog signal will be
output. The setting is made in the menu:
The following options are available:
Setting range: -20 °C to 120 °C [-4 °F to 248 °F]
Notice:

5.1.8.3 Analog output x: Assignment of the lower limit

Humidity
Assignment of the humidity level where the minimum analog signal will be output.
The setting is made in the menu:
The following options are available:
Setting range: 0% to 100%
Notice:
Temperature
Assignment of the temperature level where the minimum analog signal will be output
here. The setting is made in the menu:
The following options are available:
Setting range: -20 °C to 120 °C [-4 °F to 248 °F]
Notice:
The set output range must not be smaller than 10% of the
measurement range:
-
ai.hI
If the selected range is too small, the analog value output may have
increments.
The set output range must not be smaller than 10% of the
measurement range:
ai.hI
-
If the selected range is too small, the analog value output may have
increments.
The set output range must not be smaller than 10% of the
measurement range:
-
ai.hI
If the selected range is too small, the analog value output may have
increments.
> = 10%
ai.lO
ai.lO
> = 10% * (
0
-
100
)
> = 10%
ai.lO