Analog Outputs; Models With Analog Output; Analog Output X: Assignment Of The Upper Limit - Bosch Rexroth WGM Operating Instructions Manual

Oil humidity sensor
Table of Contents

Advertisement

Here, you can reverse the status function of the LED for a contact:
the LED is illuminated when the contact is open, i.e. below the minimum
temperature, and the status "Error" is displayed again when the LED is illuminated.
The following options are available:
LED = output;
the LED is illuminated,
when the PNP switching output
is closed.
The display function of the status LED affects the recording of events! Please refer
to the chapter "Diagnosis options".

5.1.8 Analog outputs

5.1.8.1 Models with analog output

In the factory setting, the analog output signal increases with increasing humidity.
Range adjustment and signal type are adjustable via the menu.

5.1.8.2 Analog output x: Assignment of the upper limit

Humidity
Assignment of the humidity level where the maximum analog signal will be output.
The setting is made in the menu:
The following options are available:
Setting range: 0% to 100%
Notice:
The set output range must not be smaller than 10% of the
measurement range:
If the selected range is too small, the analog value output may have
increments.
LED = output;
the LED is illuminated,
when the PNP switching output
is open.
NOTICE
-
> = 10% * (
ai.hI
ai.lO
RE 51550-B/09.2019, Bosch Rexroth AG
Operation
27/46
-
)
0
100

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents