EACIE Evacuation Alert Control and Indicating Equipment
7.5.8
Edit Zone Name
This function allows a text description to be assigned to an evacuation alert zone.
At Access Level 3 > Commissioning Functions, press the
the one shown below left appears.
To change a zone's text description, press the text description button ('Zone 1' is shown as an example) and
the window shown below right appears. Amend the text using the touchscreen's standard QWERTY keyboard
controls.
To select a different zone for editing, either press the zone number field (001 shown below left) and use the
and
buttons to scroll through the zones, or enter the zone number directly into the zone number field
using the touchscreen's numeric keypad.
7.5.9
Edit Output Group Name
This function allows text descriptions for Output Groups to be changed.
At Access Level 3 > Commissioning Functions, press the
the one shown below appears.
7.5.10
Setup Networking
This function only applies to networked panels.
7.5.11
Synchronise Network Data
This function only applies to networked panels.
7.5.12
Set Loops Fitted
This function sets the number of loops the panel's firmware assigns to a panel. Note that the actual physical
number of loops that can be connected to a panel is dependent on the number of loop driver modules fitted, i.e.
Main 1, 2 or 4-Loop PCB.
Installation and Programming Manual Approved Document No. DFU5030020 Rev 1 Page 30 of 38
Amend the text descriptions by following the same operating
procedure detailed in section 7.5.8.