EACIE Evacuation Alert Control and Indicating Equipment
7.5

Commissioning Functions

The Commissioning Functions menu is used to carry out various commissioning tasks including a loop learn
and auto address.
EACIE panel programming tools (Part No. ZTOOLS) are available on C-TEC's website
tec.com) that allow quick and easy input of data, device and zone naming.
At Access Level 3, press the
Scroll down
to view additional commissioning menu options (shown below right).
Commissioning functions are listed in sections 7.5.1 to 7.5.12.
Commissioning Note: All the loop devices connected to the EACIE panel need to have a unique address
assigning to them. In addition, the panel needs to read all the loop devices and identify their address by
performing a 'loop learn'.
There are two recommended options to do this:
Option 1: At Access Level 3 > Commissioning Functions select the Auto Address menu option.
See section 7.5.2.
The Auto Address function will automatically assign an address to each loop device in sequentially
wired order.
Note: If additional devices are later fitted to the loop, and an Auto Address is performed, you will
have the choice to:
- either continue assigning addresses from the last loop device,
- or, re-assign a new address to all the loop devices.
Option 2: First, use a CAST Hand-Held Programmer (Part No. CAPROG) to manually assign an
address to each loop device.
Second, at Access Level 3 > Commissioning Functions select the Loop Learn menu option.
See section 7.5.1.