CHAPTER 2
2.1

General Specifications

Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Compliant with
Vibration resistance
JIS B 3502 and
IEC 61131-2
Shock resistance
Operating
atmosphere
*1
Operating altitude
Installation location
Overvoltage
*2
category
*3
Pollution degree
*1
Do not use or store the programmable controller under pressure higher than the atmospheric pressure at sea level.
Doing so may cause malfunction. When using the programmable controller under pressure, please consult your local
Mitsubishi representative.
*2
This indicates the section of the power supply to which the equipment is assumed to be connected between the public
electrical power distribution network and the machinery within premises. Category II applies to equipment for which
electrical power is supplied from fixed facilities. The surge voltage withstand level for up to the rated voltage of 300V is
2500V.
*3
This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used. In pollution degree 2, only non-conductive pollution occurs. A temporary conductivity caused by an
accidental condensation may also occur occasionally.
SPECIFICATIONS
10 to 90%RH, non-condensing
Frequency
Under
5 to 8.4Hz
intermittent
8.4 to 150Hz
vibration
Under
5 to 8.4Hz
continuous
8.4 to 150Hz
vibration
Compliant with JIS B 3502 and IEC 61131-2 (147m/s
Specifications
0 to 55
-25 to 75
Constant
acceleration
2
9.8m/s
2
4.9m/s
2
, 3 times each in X, Y, and Z directions)
No corrosive gas
0 to 2000m
Inside the control panel
II or less
2 or less

CHAPTER 2 SPECIFICATIONS

Half amplitude
No. of sweeps
3.5mm
10 times each in
X, Y, and Z
directions
1.75mm
13
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nz2aw1c1by