11.2.2
Bridge module to slave module (output)
The figure below shows the time between the bridge module remote device (RY) turning on/off and the slave module
output turning on/off.
Slave module
NZ2AW1C1BY
Calculation formula
Processing time on the bridge module side + Transmission cycle time 2 + Signal delay time of the slave
module [ms]
Calculation example
Processing time on the bridge module side
Processing time of the NZ2AW1C1BY is 0.592ms. : 0.592[ms]
Transmission cycle time 2
Number of transmission points is set to 512 points: 10.2 2 = 20.4 [ms]
Signal delay time of the slave module
Signal delay time of the slave module is 0.01ms. : 0.01[ms]
Therefore, the transmission delay time is 0.592 + 20.4 + 0.01 21 [ms].
54
Ô Signal delay time of the slave module
Ó 1- to 2-transmission cycle time
Ò Processing time on the
bridge module side
Input from
the CC-Link side
Output