6.2

Remote Register List

Input or output of AnyWire Bitty uses the remote register of CC-Link.
(1) Remote register list when 1 station is occupied
Four words are used respectively for input and output of AnyWire Bitty.
Set the address for slave modules within the range from 0 to 63.
CC-Link side remote
register input
RWrn+0H
RWrn+1H
RWrn+2H
RWrn+3H
(2) Remote register list when 2 stations are occupied
Eight words are used respectively for input and output of AnyWire Bitty.
Set the address for slave modules within the range from 0 to 127.
CC-Link side remote
register input
RWrn+0H
RWrn+1H
RWrn+2H
RWrn+5H
RWrn+6H
RWrn+7H
36
AnyWire Bitty side input
address
0 to 15
16 to 31
32 to 47
48 to 63
m, n: Address assigned to the master station in the station number setting
AnyWire Bitty side input
address
0 to 15
16 to 31
32 to 47
80 to 95
96 to 111
112 to 127
m, n: Address assigned to the master station in the station number setting
CC-Link side remote
register output
RWwm+0H
RWwm+1H
RWwm+2H
RWwm+3H
CC-Link side remote
register output
RWwm+0H
RWwm+1H
RWwm+2H
RWwm+5H
RWwm+6H
RWwm+7H
AnyWire Bitty side output
address
0 to 15
16 to 31
32 to 47
48 to 63
AnyWire Bitty side output
address
0 to 15
16 to 31
32 to 47
80 to 95
96 to 111
112 to 127