Bacnet And Modbus Communications; Analog Write Points; Binary Write Points; Analog Read Only Points - York YCWL0056SE Installation Operation & Maintenance

Water-cooled liquid chillers
Table of Contents

Advertisement

SECTION 10 – MAINTENANCE
Reboot required (cycle power) after set-
tings are changed.
The table below shows the real time error numbers that
may be encountered during communication setup and a
description of each.

TABLE 28 - REAL TIME ERROR NUMBERS

ERROR
NUMBER (##)
0
ALL OK
1
DATUM TYPE OK TEST FAILED
2
ENGLISH TEXT TOO LONG
3
FLOATING POINT EXCEPTION
4
GET PACKET FAILED
5
GET TYPE FAILED
6
INVALID UNIT CONVERSION
7
INVALID HARDWARE SELECTION
8
REAL TIME FAULT
9
SPANISH TEXT TOO LONG
10
THREAD EXITED
11
THREAD FAILED
12
THREAD STALLED
13
IO BOARD RESET
14
BRAM INVALID
15
BACnet SETUP FAILED

BACnet and Modbus Communications

Chiller data that can be read and modified using spe-
cific BACnet or Modbus Register Addresses; and the
data associated with the addresses, is outlined in the
following description:

Analog Write Points

This data can be read and modified using a BACnet
or Modbus network connection. The Modbus Register
Address for these points is 1025 + AV #.

Binary Write Points

This data can be read and modified using a BACnet
or Modbus network connection. The Modbus Register
Address for these points is 1537 + BV #.
172
DESCRIPTION

Analog Read Only Points

This data can be read using a BACnet or Modbus net-
work connection and can NOT be modified using this
connection. The Modbus Register Address for these
points is 513 + AI #.

Binary Monitor Only Points

This data can be read using a BACnet or Modbus net-
work connection and can NOT be modified using this
connection. The Modbus Register Address for these
points is 1281 + BI #.
Refer to Table 29 on page 173 for complete list of
BACnet and Modbus registers.
The latest data map information is listed
on the Johnson Controls Equipment In-
tegration website.

Communications Data Map Notes:

(See Table 29 on page 173)
1. IPU II based units are configured for Native BAC-
net MS/TP and Modbus RTU communications.
Microgateway or E-Link not required for these
two communication protocols.
2. BACnet
Object Types: 0= Analog In, 1 =
Analog Out, 2= Analog Value, 3= Bina-
ry In, 4 = Binary Output, 5= Binary Value,
8= Device, 15 = Alarm Notification (0 through
127 are reserved ASHRAE Objects).
3. WC= Inches of water column; CFM = Cubic Feet
per Minute; FPM = Feet per Minute: PSI = Lbs
per square inch; Pa = Pascals; kPa = Kilopascals;
PPM = Part per Million; kJ/kg = Kilojoules per
Kilogram.
4. Water Cooled Scroll units use the same firmware
as Air Cooled Scroll units, ignoring Fan Control.
FORM 201.26-NM1
ISSUE DATE: 1/19/2018
JOHNSON CONTROLS