Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 885

Table of Contents

Advertisement

3.
Install the duct.
Fasten the connecting parts of the ducts with band, and wrap with vinyl tape to ensure no air
leaks. (Carry out the work to ensure no air leakage at a pressure of 0.80 inWG [200 Pa].)
NOTE: Do not construct the duct in the manner of below.
• Extreme bends
• Highly repetitive bends
• Making the connecting duct diameters smaller
NOTE: When wiring of the duct fan is required, refer to
7-3. Fresh air intake kit for compact cassette type
Completion figure
Indoor unit
Fresh air intake kit
- (10-33) -
Band (locally purchased)
Vinyl tape (locally purchased)
Duct (locally purchased)
Hanging band for duct
(locally purchased)
"Fresh air control output"
on page 10-28.
7. Optional parts installation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents