1-4. Address setting by remote controller

¢ Address setting by wireless remote controller
• A wireless remote controller is required to set the infrared address setting.
• Infrared address setting function is available in all indoor units with infrared signal receiver.
• Infrared address setting for duct type and cassette type models can be performed by using the op-
tional IR receiver unit.
NOTE: The beeping sound is emitted from the Indoor unit PCB. Since the indoor unit is installed
far away, the sound might not be heard. (The sound is not emitted from the IR receiver
unit.)
• The indoor unit address and the indoor unit refrigerant circuit address can be set by performing the
infrared address setting.
• When remote controller address setting is required, set by the rotary switch on the indoor unit
PCB.
 Preparation
1.
(This step is unnecessary for newly installed and not yet set the switch.)
Set the rotary switch on the indoor unit PCB for manual address setting. (Initially set to "00" as
factory setting.)
The layout of the switches differs by the type of the indoor unit. For the details, refer to
on indoor unit PCB"
2.
Before turning on the power of indoor unit, reconfirm following items:
• Piping air tight test and vacuuming have been performed firmly.
• There is no wiring mistake.
3.
Turn on the power of indoor units.
By turning on the power, the indoor units initialize EEV.
Breaker ON
1-4. Address setting by remote controller
on page 07-67.
SW604 SW605 SW606 SW607 SW608
SW601
SW602
Check the switch position is set at "0".
(Factory setting)
Indoor units
- (07-15) -
Rotary switch
(type A)
IU AD x10
IU AD x1
REF AD x10
REF AD x1
"Setting
Indoor units
1. System settings