Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 103

Table of Contents

Advertisement

4. Installation space
CAUTION
• The installation space shown in the following examples is based on an ambient temperature un-
der cooling operation of 95°FDB (35°CDB) at the air intake of the outdoor unit.
Provide more space around the air intake than shown in the examples if the ambient tempera-
ture exceeds 95°FDB (35°CDB) or if the thermal load of all of the outdoor units exceeds the ca-
pacity.
• Consider the transportation route, installation space, maintenance space, and access, and in-
stall the unit in a location with sufficient space for the refrigerant piping.
• Observe the installation space specifications that are shown in the figures.
Provide the same space for the air intake at the rear of the outdoor unit.
If the installation is not performed according to the specifications, it could cause a short circuit
and result in a lack of operating performance. As a result, the outdoor unit might easily be
stopped by high-pressure protection.
• When there is a wall at the right side of the unit, provide a space of 8 in (200 mm) or more.
• Installation methods not shown in the following examples are not recommended. Performance
may drop significantly.
Front
Rear
Air intake
- (03-7) -