Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 554

Table of Contents

Advertisement

• Limitation check
Total pipe length
Between outdoor unit and farthest indoor
unit
Between the first separation tube and the
farthest indoor unit
Between outdoor unit and the nearest
indoor unit
Between outdoor unit and the first
separation tube
• Calculation of additional charge refrigerant
– Calculation of additional amount for pipe length (A)
Diameter of liquid pipe
in (mm)
Ø1/2 (12.70)
Ø3/8 (9.52)
Ø1/4 (6.35)
A = (0.077 lb × 232 ft) + (0.039 lb × 42 ft) + (0.014 lb × 19 ft) = 19.768 (lb)
A = (0.114 kg × 71 m) + (0.058 kg × 13 m) + (0.021 kg × 6 m) = 8.974 (kg)
– Calculation of factory charge amount (B)
Outdoor unit
B = 24.25 lb (11.0 kg)
– Total refrigerant amount check (C)
C = A + B = 19.768 + 24.25 = 44.019 (lb) < 44.09 (lb) → OK
C = A + B = 8.974 + 11.0 = 19.974 (kg) < 20.0 (kg) → OK
Check pipe length and height difference between the units by comparing with
page 06-17.
2-6. Piping design example
Pipe
Additional amount for pipe
1
Example
Diagram
Total
295 (90)
a + b3
255 (78)
b3
22 (7)
a + b1
252 (77)
a
232 (71)
length
lb/ft (kg/m)
0.077 (0.114)
0.039 (0.058)
0.014 (0.021)
Model name
AOU96RLAVL
- (06-32) -
Limitation
Judge
ft (m)
1,312 (400)
OK
or less
393 (120)
OK
or less
295 (90)
OK
or less
17 (5)
OK
or more
10 (3)
OK
or more
Liquid pipe length
ft (m)
232 (71)
42 (13)
19 (6)
Factory charge amount
24.25 lb (11.0 kg)
"Piping limitation"
2. Piping design