Fujitsu AIRSTAGE J-IIIL Design & Technical Manual page 700

Table of Contents

Advertisement

Function
Function
number
External
heater use
75
in defrosting
Range of static pressure mode by model
Model name
ARUL4TLAV1
ARUL7TLAV2
ARUL9TLAV2
ARUL12TLAV2
ARUL14TLAV2
ARUL18TLAV2
ARUM24TLAV2
ARUM30TLAV2
ARUM36TLAV2
ARUH36TLAV
ARUH48TLAV
ARUH60TLAV
ARUH72TLAV2
ARUH96TLAV2
Temperature conditions when the external heater is on/off
Temperature (t) = Room temperature - set temperature
External heater: On
00
01
02
03
04
05
06
07
Set value
08
of
function:
09
62
10
11
12
13
14
15
16
17
2-9. Function details
Factory
Setting number
00
Disabled
01
Enabled
Range of static pressure mode
SP mode 00 to 03
SP mode 00 to 09
SP mode 00 to 14
SP mode 00 to 11
SP mode 00 to 09
Setting prohibited
because of AC motor
SP mode 05 to 30
SP mode 05 to 29
00
External heater: Off
t < -5.4 °F (-3 °C)
t ≥ -1.8 °F (-1 °C)
t < -3.6 °F (-2 °C)
t ≥ -1.8 °F (-1 °C)
t < -3.6 °F (-2 °C)
t ≥ -1.8 °F (-1 °C)
t < -5.4 °F (-3 °C)
t ≥ -1.8 °F (-1 °C)
t < -7.2 °F (-4 °C)
t ≥ -1.8 °F (-1 °C)
t < -9.0 °F (-5 °C)
t ≥ -1.8 °F (-1 °C)
t < -5.4 °F (-3 °C)
t ≥ -0.9 °F (-0.5 °C)
t < -3.6 °F (-2 °C)
t ≥ -0.9 °F (-0.5 °C)
t < -3.6 °F (-2 °C)
t ≥ -0.9 °F (-0.5 °C)
t < -5.4 °F (-3 °C)
t ≥ -0.9 °F (-0.5 °C)
t < -7.2 °F (-4 °C)
t ≥ -0.9 °F (-0.5 °C)
t < -9.0 °F (-5 °C)
t ≥ -0.9 °F (-0.5 °C)
t < -5.4 °F (-3 °C)
t ≥ 0 °F (0 °C)
t < -3.6 °F (-2 °C)
t ≥ 0 °F (0 °C)
t < -3.6 °F (-2 °C)
t ≥ 0 °F (0 °C)
t < -5.4 °F (-3 °C)
t ≥ 0 °F (0 °C)
t < -7.2 °F (-4 °C)
t ≥ 0 °F (0 °C)
t < -9.0 °F (-5 °C)
t ≥ 0 °F (0 °C)
setting
Enables or disables the external heater use in
defrosting.
NOTE: When using function number 75,
inappropriate heater selection may cause
cold air in defrosting.
Set value of function: 61
External heater: On
t ≤ -0.9 °F (-0.5 °C)
t ≤ -1.8 °F (-1 °C)
t ≤ -3.6 °F (-2 °C)
t ≤ -5.4 °F (-3 °C)
t ≤ -7.2 °F (-4 °C)
t < -9.0 °F (-5 °C)
t ≤ -0.9 °F (-0.5 °C)
t ≤ -1.8 °F (-1 °C)
t ≤ -3.6 °F (-2 °C)
t ≤ -5.4 °F (-3 °C)
t ≤ -7.2 °F (-4 °C)
t < -9.0 °F (-5 °C)
t ≤ -0.9 °F (-0.5 °C)
t ≤ -1.8 °F (-1 °C)
t ≤ -3.6 °F (-2 °C)
t ≤ -5.4 °F (-3 °C)
t ≤ -7.2 °F (-4 °C)
t < -9.0 °F (-5 °C)
- (07-100) -
Details
Normal static pressure
0.04 inWG (10 Pa)
0.10 inWG (25 Pa)
0.16 inWG (40 Pa)
0.40 inWG (100 Pa)
0.60 inWG (150 Pa)
01 to 99
External heater: Off
t ≥ 0.9 °F (0.5 °C)
t ≥ 0.9 °F (0.5 °C)
t ≥ 0.9 °F (0.5 °C)
t ≥ 0.9 °F (0.5 °C)
t ≥ 0.9 °F (0.5 °C)
t ≥ 0.9 °F (0.5 °C)
t ≥ 0 °F (0 °C)
t ≥ 0 °F (0 °C)
t ≥ 0 °F (0 °C)
t ≥ 0 °F (0 °C)
t ≥ 0 °F (0 °C)
t ≥ 0 °F (0 °C)
t ≥ -0.9 °F (-0.5 °C)
t ≥ -0.9 °F (-0.5 °C)
t ≥ -0.9 °F (-0.5 °C)
t ≥ -0.9 °F (-0.5 °C)
t ≥ -0.9 °F (-0.5 °C)
t ≥ -0.9 °F (-0.5 °C)
2. Function settings

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents