Omron sysmac NJ Series Connection Manual page 42

Machine automation controller, displacement sensor
Hide thumbs Also See for sysmac NJ Series:
Table of Contents

Advertisement

7.3.6.
Transferring the Project Data
Connect online and transfer the connection settings and the project data to Controller.
When you transfer a user program, configuration data, setup data, device
variables, or values in memory used for CJ-series Units from Sysmac Studio,
the devices or machines may perform unexpected operation regardless of the
operating mode of CPU Unit.
Always confirm safety at the destination node before you transfer the project
data.
1
Turn ON Controller, Switching
hub, and Sensor Controller.
2
Select Check All Programs
from the Project Menu.
3
The Build Tab Page is
displayed.
Check that "0 Errors" and "0
Warnings" are displayed.
4
Select Rebuild Controller from
the Project Menu.
5
A confirmation dialog box is
displayed. Check the contents
and click Yes.
6
Check that "0 Errors" and "0
Warnings" are displayed on the
Build Tab Page.
7.EtherNet/IP Connection Procedure