Wiring Trane Zone Sensors - Trane Tracer UC600 Installation, Operation And Maintenance Manual

Hide thumbs Also See for Tracer UC600:
Table of Contents

Advertisement

Wiring Inputs and Outputs

Wiring Trane Zone Sensors

The table in
application.
1. Connect the shield to a common terminal at the terminal board device.
2. Connect the zone sensor wires to any available input (UI, UIO) terminals; refer to table 7 as an
3. Use the Tracer TU service tool to configure the analog input that references the corresponding
Figure 14. Typical wiring, Trane zone sensors
Space
1
2
Setpoint
3
Fan mode
4
34
Figure 14
shows the terminations on a Trane zone sensor and a typical UC600
Note: Do Not use the shield as the common connection. For 3-wire applications, use a
3-conductor cable with shield and for 2-wire applications, use a 2-conductor cable with
separate shield.
example.
hardware termination.
IM C
24
VAC
XFMR
1
U C 600
B O 1
B O 2
B O 3
ADDRESS
x100
x10
AO1
UI 9
Table 10. Example zone sensor terminations
Zone Sensor
Zone Sensor
Termination
Output
1
Zone Temp
2
Ground
Zone Temp
3
Setpoint
4
Fan Mode
Note: Example hardware terminations. Any universal input or universal
input/analog output may be used for terminating zone temp, zone temp
setpoint, or fan mode.
24
24
VAC
VAC
OUT
MBUS
OUT
UI 1
UI 2
UI 3
UI 4
UI 5
B O 4
x1
AO 2
AO 3
AO 4
AO 5
AO 6
UI 10
UI 11
UI 12
UI 13
UI 14
UC600
Termination
Type
UI1
Thermistor
n/a
UI2
Resistive
UI3
Resistive
+ 24
+ 24
VDC
VDC
OUT
UI 6
UI 7
UI 8
RELAYS 0 . 5 A MAX
BO 1
BO 2
BO 3
Range
10kΩ
n/a
200Ω−20kΩ
200Ω−20kΩ
IM C
+ 24
VDC
LINK
IMC
P 1
LINK
MBUS
IM C
TX
RX
LINK
SERVI C E
ACT
SERVICE TOOL
BO 4
BAS-SVX45F-GB