Additional Components; Water, Discharge, And Outdoor Air Temperature Sensors; Binary Input Switching Devices; Zone Temperature Sensors - Trane Tracer UC400 Installation, Operation And Maintenance Manual

Water source heat pump (wshp)
Table of Contents

Advertisement

Additional Components

The UC400 Controller requires the use of additional components for monitoring and proper
control of associated equipment. The use of specific components is dependent on the type of
application.
N N o o t t e e : : Additional components are not included with the UC400 Controller.

Water, Discharge, and Outdoor Air Temperature Sensors

Temperature sensors must be Trane 10 kΩ (at 25°C) thermistors. Entering water and discharge air
inputs can use a sealed temperature sensor (part numbers 4190 1100 and 4190 1133).

Binary Input Switching Devices

Occupancy, condensate overflow, compressor protection, frost detection, and fan status inputs
accept switching devices that may have normally open (NO) or normally closed (NC) dry
contacts.

Zone Temperature Sensors

The following table provides the sensor types and features supported by the UC400 Controller.
Table 3. UC400 controller supported sensors and features
Sensor
Setpoint
Type
Temperature
No
Sensor
No
Single
Single
Temperature
Sensors w/
Fan Control
Single
Temperature
Sensor w/
Single
LCD Display
(a)
10
Features
Fan
System
Control
No
No
Off
Auto
Off
Auto
Low
No
High
Off
Auto
Low
Medium
High
Off
Auto
No
Low
Medium
High
Occupancy
LEDs
No
No
Yes
Yes
Yes
No
Yes
Can be
configured
No
for
occupancy
Part
BAYSENS
Number
X1351152801
BAYSENS077A
X1351153001
BAYSENS073A
X1379084501
X1379084801
N/A
X1379084201
X1379088604
N/A
Global
Parts
SEN01448
SEN01450
SEN01521
SEN01524
SEN01518
N/A
BAS-SVX065E-EN