Creating Points For Timed Override (Tov) And */** Functions - Trane Tracer UC600 Installation, Operation And Maintenance Manual

Hide thumbs Also See for Tracer UC600:
Table of Contents

Advertisement

Configuring Tracer UC600 with Tracer TU
Figure 25. Creating multistate points to monitor communication status
Select an XM
module from the
Device node

Creating Points for Timed Override (TOV) and */** Functions

Functionality for TOV and */** (thumb wheel) functions can be configured for the UC600, UC400,
and the XM70. This is required in order for TGP2 when creating programs for TOV and */***. After
creating points as described below, see
To create points for TOV functions
1. Open a session of Tracer TU.
2. Select the Controller Settings Utility tab from the vertical tab set located on the right side of the
3. Select the Analog tab.
4. Click Create on the Analog Value title bar. The Point Properties dialog box appears.
5. In the Point Properties dialog box, enter a meaningful name in the Name field.
6. Click on the button in the Reference field. The Reference dialog box appears.
7. Select a point to reference, then select analog value from the Available Properties frame. Click
8. In the Definition frame, select the Create an associated Multistate Input check box.
9. The required multistate input is automatically created
10. Click Send to Device to send the new point configuration to the controller.
50
Tracer TU window.
OK.
"Enabling TOV and */** for TGP2 Programs, " p.
(Figure 26, p.
51.
51).
BAS-SVX45F-GB

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bmuc600aaa0100011

Table of Contents