Wiring and Powering the Tracer UC600

Controller Startup and Power Check

1. Verify that the 24 VAC connector and the chassis ground are properly wired.
2. Remove the 24 VAC connector from the Tracer UC600.
3. Remove the lockout/tagout from the line voltage power to the electrical cabinet.
4. Using a digital multimeter (DMM), verify that 24 VAC is present at the 24 VAC connector.
The following table describes the Tracer UC600 service and power LED indicators.
Table 8.
26
If voltage reading is within plus or minus 10%, connect the 24 VAC connector to the transformer
XMRF input on the UC600.
LED startup sequence
Power LED
Indicates...
Solid Green
Normal operation.
Blinking Red
Alarm or fault is present.
Solid Red
Low voltage or malfunction.
Sequence on Powerup: Illuminates red, then green.
Service LED
Indicates...
Solid Green
LED has been pressed and remains on until powered down.
Blinking Green
Controller not accessing application software.
Not illuminated
Normal operation.
Sequence on Power-up: Does not illuminate during power-up.