Emerson Rosemount 702 Quick Start Manual page 43

Wireless discrete transmitter
Hide thumbs Also See for Rosemount 702:

Advertisement

April 2018
Standards: Class 3600 - 2011,Class 3610 - 2010, Class 3611 - 2004,Class
Markings:
Special Conditions for Safe Use (X):
1. The Rosemount 702 Transmitter housing contains aluminum and is
considered a potential risk of ignition by impact or friction. Care must be
taken into account during installation and use to prevent impact and
friction.
2. The surface resistivity of the polymeric antenna is greater than 1GΩ. To
avoid electrostatic charge build-up, it must not be rubbed or cleaned with
solvents or a dry cloth.
3. The model 702 may only be used with either the 701PBKKF Rosemount
Smartpower Black Power Module or the Computational Systems, Inc.
(CSI) MHM-89004.
Sensor terminal parameters (option code
32)
U
= 6.6 V
O
I
= 13.37 mA
O
P
= 21.77 mW
O
C
= 21.78 µF
O
L
= 198 mH
O
7.6.2
N5 U.S.A. Nonincendive
Certificate: [CSA] 1143113
Standards: Class 3600 - 2011, Class 3611 - 2004, Class 3810 - 2005, UL
Markings:
Special Conditions for Safe Use (X):
1. The model 702 may only be used with either the 701PBKKF Rosemount
Smartpower Black Power Module or the Computational Systems, Inc.
(CSI) MHM-89004.
Quick Start Guide
3810 - 2005, UL 50E (11th Edition), UL 61010-1 (3rd Edition),
ANSI/ISA-60079-0 (12.00.01) - 2013, ANSI/ISA 60079-11
(12.02.01): 2014, ANSI/IEC 60529-2004
IS CL I, DIV 1, GP, A, B, C, D; CL II, DIV 1, GP E, F, G; Class III;
Class 1, Zone 0 AEx ia IIC Ga T4; NI CL I, DIV 2, GP A, B, C, D T4;
T4(–50 °C ≤ T
≤ +70 °C) when installed per Rosemount
a
drawing 00702-1020; Type 4X/IP66/67
50E (11th Edition), UL 61010-1 (3rd Edition), ANSI/IEC
60529-2004
NI CL I, DIV 2, GP A, B, C, D T4; T4(-50 °C ≤ T
4X/IP66/67
Fuel sensor terminal parameters (option
code 61)
U
= 7.8 V
O
I
= 92 mA
O
P
= 180 mW
O
C
= 9.2 µF
O
L
= 4.2 mH
O
Quick Start Guide
≤ +70 °C) Type
a
43