Figure 5-21:
A. TT‐MLC‐MC‐BLK (Leader Cable)
B. TT5000/TT5001 Sensor cable (up to 500 ft.)
C. TT‐MET‐MC (End termination)
D. TT‐MJC‐xx‐MC‐BLK (Optional jumper cable)
E. TT‐ZBC‐xx‐MC‐BLK (Branch connector)
F. TT‐MET‐MC (End termination)
G. TT‐MET‐MC (End termination)
H. Up to 500‐ft. TT5000 or TT5001 sensor cable (Total per 702)
Important notes regarding the use of Tyco TraceTek Fast Fuel Sensor and
TraceTek sensing cable:
Tyco TraceTek sensors must be installed as per manufacturer
recommendations.
Do not run the Rosemount 702 Transmitter for long periods (more than
two weeks) with a Tyco fuel sensor in the leak state as this will more
rapidly deplete the power module.
5.9.3
Liquid hydrocarbon detection interface, for Modbus
Table 5‐5
detection in other communications protocols such as Modbus or OPC. It is
imperative that both PV and SV be mapped to the host system so as to make
a good interpretation of the condition and status of the leak detector.
Quick Start Guide
Fuel Sensor Cable Wiring
describes use of the Rosemount 702 Transmitter for hydrocarbon
Quick Start Guide
®
mapping