www.plcworld.cn
3 SPECIFICATION
Device No.
RX(n+1)A
RX(n+1)B
RYn0
to
RYn3
RY(n+1)8
RY(n+1)9
RY(n+1)A
Table 3.5 Remote I/O Signal Details (2/2)
Signal Name
Error status flag
Remote READY
CH.
moving average
processing specifying flag
Initial data processing
completion flag
Initial data setting request
flag
Error reset request flag
range error flag (RXn4 to RXn7) or E
Turns on when CH.
(RXnC) has turned on.
Does not turn on at occurrence of the watchdog timer error. ("RUN" LED goes off.)
RX(n+1)A
Error status flag
RXn4 to RXn7
CH.
range error flag
RY(n+1)A
Error reset request flag
: Performed by sequence ladder
: Performed by AJ65SBT-64AD
Turns on when initial data setting is completed after power-on or at termination of the
test mode.
(Used for interlocking read/write from/to the master module.)
Set the A/D conversion system to sampling processing or moving average
processing per channel.
Made valid on the leading edge of the initial data setting request flag (RY(n+1)9).
OFF: Sampling processing
ON: Moving average processing
Turns on after initial data processing completion when initial data processing is
requested after power-on or test mode operation.
Turns on at the time of initial data setting or changing.
When this flag turns on, the CH.
off) and the error status flag (RX(n+1)A) is also reset, but the E
flag (RXnC) cannot be rest and therefore the error status flag remains on.
n: Address allocated to the master module by the station number setting.
3 - 12
MELSEC-A
Description
2
PROM write error flag
range error flag (RXn4 to RXn7) is reset (turned
2
PROM write error