www.plcworld.cn
5. PROGRAMMING
Procedure execution condition
Initial data processing request flag (RX78) turns ON
Initial data processing request flag (RX78) turns OFF
Initial data setting completion flag (RX79) turns OFF
(2) Initial setting by remote device station initialization procedure registration function
(a) Target station number setting
Set the target station number of initial setting.
Set the target station number to "1".
(b) Procedure registration setting
The initial setting is registered to the AJ65BT-64RD when the initial data processing request
flag (RX78) turns ON and Remote device station initialization procedure registration (SB0D) is
set.
The following table indicates the setting results of the initial setting.
POINT
(1) When the remote device station initialization procedure registration command (SB000D) is
turned OFF after initial processing, all the RY signals that turned ON in the initial procedure
registration turn OFF. Hence, turn ON the "CH.
program.
(2) When the initial setting (CH.
flag, offset/gain selection flag) is changed, the remote device station initialization procedure
registration function cannot be used.
Use a sequence program to change the initial setting.
(c) Setting result
The setting result is shown below.
Execution
CH. 1 sampling processing/travel average processing
designation flag is set to the travel average processing.
(RY04: ON)
CH. 2 sampling processing/travel average processing
designation flag is set to the travel average processing.
(RY05: ON)
Offset/gain value selection flag is set to the factory setting.
(RY77: ON)
Initial data processing completion flag (RY78) is turned ON.
Initial data setting request flag (RY79) is turned ON.
Initial data processing completion flag (RY78) is turned OFF.
Initial data setting request flag (RY79) is turned OFF.
conversion enable flag" in a sequence
sampling processing/travel average processing designation
5-6