Maintenance

10.4 ERROR CODES

This section describes off-line error codes, on-line error codes, and on-line status codes. Typically, a code will
point to a failed internal assembly or a failed peripheral device. Note that a configuration error can also cause an
error code or multiple error codes to be produced. For example, an error will occur when attempting to run a
configuration that includes an I/O Expander board hardware I/O block (i.e. AINU 1, AINU2, DINU1, DINU2,
ROUT1 or ROUT2) in a controller that does not have an I/O Expander board installed.

10.4.1 Off-Line Error Codes

Off-line error messages are displayed while the 353 is powered but not running function block code and therefore
not actively controlling a process. Depending on the message, user intervention will most likely be required.
Corrective action can be initiated via the Ethernet or Modbus ports as appropriate. Parameter "SE" located at
Modbus register 40002 will contain the hexadecimal form of the error number currently displayed (e.g., ERR: 213
would be sent as $00D5). An Error message can be acknowledged over the network by writing a 0 to the Modbus
register. Messages are displayed one at a time, in order of occurrence, and a message cannot be cleared until the
error condition is corrected.
ERROR
DESCRIPTION
CODE
101
Board type test
102
DRAM error
103
SRAM error
104
Flash CRC error
202
Constant Data CRC Test
203
Calibration Data CRC Test
205
Database Compatibility Test
208
Board Compatibility Test
213
Calibration Data CRC Test
214
Software Compatibility Test
215
Database Compatibility Test
216
Board Not Present
218
Board Compatibility Test
10-6
Table 10-1 Off-Line Error Codes
CORRECTIVE ACTION
Replace Controller board.
Replace Controller board.
Replace Controller board.
Press ENTER to reset and retest controller. If error remains, replace
Controller board or reinstall firmware.
Controller operation suspended. Press ENTER to load Controller
board default constant data.
Controller operation suspended. Press ENTER to load Controller
board default calibration data.
Controller operation suspended. Press ENTER to, if possible, convert
the database or load Controller board default constant data.
Install compatible Controller board.
Controller operation suspended. Press ENTER to load I/O Expander
board default calibration data.
Controller operation suspended. Replace I/O Expander board or press
ENTER to remove from the configuration all references to blocks
relating to the Expander board.
Controller operation suspended. Replace I/O Expander board or press
ENTER to, if possible, convert the database or load Expander board
default constant data.
Controller operation suspended. Install I/O Expander board or press
ENTER to remove from the configuration all references to the
missing board.
Install compatible I/O Expander board.
UM353-1
April 2012