3.2.87 SUB_ - Subtraction
SUB_ function blocks perform arithmetic subtraction on
the two input signals. Any unused input will be set to 0.0.
All inputs should have the same engineering units. If units
are not consistent, a SCL function block can be used or an
alternative is to use a MTH function block that has built-in
scaling functions.
A
Input A
.
B
Input B
BLOCK DIAGRAM
3.2.88 TAN_ - TANGENT
TAN__ function blocks accept a radian input and output the
tangent of that angle.
X
.
Input X
April 2012
+
O utput 1
-
Rev 2
TAN (X)
O utput 1
BLOCK DIAGRAM
SUBTRACTION
A
Input A
B
Input B
I
N
P
U
T
A
I
N
P
U
T
B
E
S N
O1
.
TANGENT
Input X
O1
I
N
P
U
T
.
E
Function Blocks
SUB_
ESN = 000
SUBTRACTION
O1
Output 1
INPUT A
..........
loop tag.block tag.output
(H)
INPUT B
..........
loop tag.block tag.output
(H)
Exec. Seq. No.
................ 001 to 250
(H)
TAN
ESN = 000
X
O1
Output 1
O
= TAN (X)
1
X
INPUT X ..............
loop tag.block tag.output
S N
Exec. Seq. No. ..................... 000 to 250
(null)
(null)
(null)
(000)
3-89