Scl_ - Scaler; Sel_ - Signal Selector - Siemens 353 User Manual

Process automation controller
Hide thumbs Also See for 353:
Table of Contents

Advertisement

UM353-1B

3.2.80 SCL_ - Scaler

SCL_ function blocks provide a means to scale an analog
signal. It will re-range a signal by using the range pointer
to reference the function block with the original range.
When the range pointer (input R) is not configured, the
function block will not re-scale the input signal but will
pass it directly to the output. The purpose, under this
situation, would be to provide minimum and maximum
scale, preferred decimal point position, and units for
another block (e.g. operator display) to reference.
+
Output MAX SCALE - Output MIN SCALE
A
Input MAX SCALE - Input MIN SCALE
-
.
Input MIN SCALE
Input RanGe PoinTeR
BLOCK DIAGRAM

3.2.81 SEL_ - Signal Selector

SEL_ function blocks can provide a high or low signal
selection on the three input signals. Unused inputs will be
set equivalent to the lowest real value when configured as a
HI selector and to the highest real value when configured as
a LO selector.
A
Input A
SELECTOR
B
Input B
C
Input C
BLOCK DIAGRAM
April 2012
+
+
Output MIN SCALE
ENGingeering UNITS
Rev 2
SIGNAL
Output
HI/LO
SCALER
R
Range
A
Analog Input
R
G
P T R
M I N S
C A L E
M A X S C A L E
D P P
E N G
U
N
I
T
S
N
U
T
I
P
A
E S N
O1
SIGNAL SELECTOR
Input A
A
Input B
B
C
Input C
S E
L
T
Y
P
I N
P
U
T
I
N
P
U
T
O1
I
N
P
U
T
E S N
Function Blocks
SCL_
ESN = 000
OR
Output Range
SCALER
O1
Output 1
RanGe PoinTeR
..........
loop tag.block tag
(S)
Output MINimum SCALE
............ Real (0.00)
(H)
Output MAXimum SCALE
........... Real (100.00)
(H)
D
ecimal
P
t.
P
osition (preferred)
... 0.0.0.0.0.0
(S)
ENGineering UNITS
...... 6 ASCII Char (PRCT)
(S)
INPUT A
.............
loop tag.block tag.output
(H)
Exec. Seq. No.
................... 001 to 250
(H)
ESN = 000
SEL_
SIGNAL
O1
Output 1
SELECTOR
E
SELector TYPE
.................... LO/HI
(S)
A
INPUT A
.......
loop tag.block tag.output
(H)
B
INPUT B
.......
loop tag.block tag.output
(H)
C
INPUT C
.......
(H)
loop tag.block tag.output
.............. 001 to 250
Exec. Seq. No.
(H)
(null)
(0.00)
(null)
(LO)
(null)
(null)
(null)
3-85