Sin_ - Sine; Splim - Setpoint Limit - Siemens 353 User Manual

Process automation controller
Hide thumbs Also See for 353:
Table of Contents

Advertisement

UM353-1B

3.2.83 SIN_ - SINE

SIN__ function blocks accept a radian input and output the sine
of that angle.
X
.
Input X

3.2.84 SPLIM - Setpoint Limit

SPLIM function blocks can be used on a one per loop
basis to limit the setpoint of the loop controller. Input A
will pass through the function block to output O1 unless it
equals or exceeds the High limit setting or exceeds the
Low limit setting at which time the block will output the
limit value.
If the HI LIMIT is set lower than the LO LIMIT, the block
will always output the high limit value.
Output status HS or LS will be high (1) if the block is in a
limit condition. The status event 'S HI LIM' or 'S LO
LIM' will be displayed in the alphanumeric if the SL
PRIOR is greater than 0. A priority of 0 disables the
reporting of the limit function and sets the bits in the status
word to 0. See the table on the next page for additional
details regarding priorities.
The SPLIM function block has an RG PTR parameter (input R) that defines the normal operating range of the
block. Limit settings can be made within -10% to 110% of the range pointer values. If the range pointer is not
configured, a range of 0.0 to 100.0 will be used. If a range change is made the current limit value will be moved to
be the same % value within the new range.
A
.
April 2012
O1
SIN (X)
Output 1
BLOCK DIAGRAM
HI SELECTOR
LO LIMIT
BLOCK DIAGRAM
SINE
X
Input X
.
I
N
P
U
T
X
E
S N
SETPOINT LIMIT
SPLIM
R
Range
SETPOINT LIMIT
A
Input A
R G
P T R
RanGe PoinTeR
H I
L
I
M
I
T
HIgh LIMIT
L
O
L I M I T
LOw LIMIT
I N
P
U
T
A
INPUT A
S
L
P
R
I
O
R
Setpt Limit PRIORity
E S N
Exec. Seq. No.
LO SELECTOR
Output 1
High limit Status
Low limit Status
HI LIMIT
Function Blocks
SIN
ESN = 000
O1
O utput 1
O
= SIN (X)
1
INPUT X ..............
loop tag.block tag.output
(null)
E xec. S eq. N o. ..................... 000 to 250
(000)
ESN = 000
O1
Output 1
HS
High Status
LS
Low Status
..
loop tag.block tag
(null)
(H)
........................... Real (100.00)
(S)
........................... Real
(0.00)
(S)
.....
(H)
loop tag.block tag.output
(null)
.. 0,1,2,3,4,5
(0)
(S)
........... 001 to 250
(H)
O1
HS
.
LS
.
3-87