Fco101 - Single Loop Controller W/ Tracking Setpoint - Siemens 353 User Manual

Process automation controller
Hide thumbs Also See for 353:
Table of Contents

Advertisement

Factory Configured Options

4.1 FCO101 - Single Loop Controller w/ Tracking Setpoint

Factory Configured Option FCO101 provides a single loop controller configured in Loop01. A block diagram of
the loop configuration is shown below along with any changes to the default parameter values of the configured
blocks. This configuration provides setpoint tracking which will cause the setpoint to track the process when the
loop is not in Auto (NA). If the loop tag 'Loop01' is changed, all configured references within the station will
automatically be changed to the new tag.
TV
TC
SR
LU
LD
Process
O1
AIN1
QS
.
P
D
SETPT - Setpoint Function Block
RG PTR - Range Pointer ----------- Loop01.AIN1.OR
INPUT TV - Input TV -------------- Loop01.AIN1.O1
INPUT TC - Input TC -------------- Loop01.A/M.NA
ESN - Exec. Seq. No.--------------- 5
ALARM - Alarm Function Block
RG PTR - Range Pointer ---------- Loop01.AIN1.OR
INPUT P - Input P ----------------- Loop01.AIN1.O1
INPUT D - Input D ---------------- Loop01.SETPT.O1
ESN - Exec. Seq. No. ------------- 10
PID - PID Controller Function Block
RG PTR - Range Pointer ---------- Loop01.AIN1.OR
INPUT P - Input P ----------------- Loop01.AIN1.O1
INPUT S - Input S ----------------- Loop01.SETPT.O1
INPUT F - Input F ----------------- Loop01.A/M.O1
INPUT A - Input A ---------------- Loop01.A/M.AS
ESN - Exec. Seq. No.-------------- 15
4-2
SETPT
O1
P
A1
A2
ALARM
A3
A4
S
P
O1
A
S
AE
TV
PID
A/M
F
AW
TC
A
EM
I
A/M - Auto/Manual Function Block
RG PTR - Range Pointer ------------ Loop01.PID.OR
INPUT A - Input A ------------------- Loop01.PID.O1
ESN - Exec. Seq. No. --------------- 20
AOUT1 - Analog Output 1 Function Block
RG PTR - Range Pointer ------------ Loop01.PID.OR
INPUT S - Input S ------------------- Loop01.A/M.O1
ODC - Operator Display for Controllers
P RG PTR - P Range Pointer ------- Loop01.AIN1.OR
V RG PTR - V Range Pointer ------ Loop01.PID.OR
INPUT P - Input P (Process) ------- Loop01.AIN1.O1
INPUT S - Input S (Setpoint) ------ Loop01.SETPT.O1
INPUT V - Input V (Valve) -------- Loop01.A/M.O1
LOOP #- Loop # ------- 01
UM353-1B
Valve
O1
S
AOUT1
AS
D
NA
QS
MS
.
ES
SS
V
LOOP01
April 2012