Installation
Terminal Function, ID, and Number
Network Communications A, NCA, 3
Network Communications B, NCB, 4
Transmitter Power 26 Vdc+, XMTR+, 5
Transmitter/Station Common, COM, 6
Transmitter Power, 26 Vdc+, XMTR+, 7
Digital Output 1+, DOUT1+, 8
Digital Outputs 1/2 Common, DOUTC, 9
Digital Output 2+, DOUT2+, 10
Digital Input 1+, DIN1+, 11
Digital Input 1-, DIN-, 12
Digital Input 2+, DIN2+, 13
Digital Input 2-, DIN2-, 14
Digital Input 3+, DIN3+, 15
Digital Input 3-, DIN3-, 16
Analog Output 1+, AOUT1+, 17
Analog Output 1/2 Common, AOUTC, 18
Analog Output 2+, AOUT2+, 19
Analog Input 1+, AIN1+, 20
Terminal Function, ID, and Number
Analog Input 1/2 Common, AINC, 21
Analog Input 2+, AIN2+, 22
Analog Input 3+, AIN3+, 23
Analog Input 3 Common, AINC, 24
I/O Bus A, IOA (design level A only), 25
I/O Bus B, IOB (design level A only), 26
Relay Output 1 Normally Closed, ROUT1nc, 27
Relay Output 1 Common, ROUT1c, 28
Relay Output 1 Normally Open, ROUT1no, 29
Relay Output 2 Normally Closed, ROUT2nc, 30
Relay Output 2 Common, ROUT2c, 31
Relay Output 2 Normally Open, ROUT2no, 32
Analog Output 3+, AOUT3+, 33
Analog Output 3 Common, AOUTC, 34
Notes:
1. Terminal numbers are shown on each connector. The plug-in portions of the connectors are packed with a case.
The connectors are keyed.
2. Case/Safety Ground - Connect to green screw at top center of rear terminal area.
3. NCA and NCB - Connect Modbus cable or twisted pair wiring. Refer to UM353-1B, Section 7.4.9 for
additional details.
4. IOA and IOB - No connection
5. Ground Bus - An external, user-supplied ground bus can ease connection of multiple grounds, particularly when
twinaxial cable shields are to be grounded.
6. Terminals 6, 9, 18, 21, 24, 34, 40, and 42 are electrically connected. Use the terminals that allow the best wire
routing and the least stress on components, such as range resistors.
Figure 7-5 Rear Terminal Layout and Terminal Assignments
7-8
Case/Safety Ground
Power Input
AC Hot or DC+, H
AC Neutral or DC-, N
Ethernet
Connector
Terminal Number, Function, and ID
35, Digital Input Universal 1+, DINU1+
36, Digital Input Universal 1-, DINU1-
37, Digital Input Universal 2+, DINU2+
38, Digital Input Universal 2-, DINU2-
39, Transmitter Power 26 Vdc+, XMTR+
40, Transmitter/Station Common, COM
41, Analog Input 4+, AIN4+
42, Analog Input Common, AINC
43, Digital Input 4+, DIN4+
44, Digital Input 4-, DIN4-
45, Analog Input Universal 1 a, AINU1a
46, Analog Input Universal 1 b, AINU1b
47, Analog Input Universal 1 c, AINU1c
48, Analog Input Universal 1 d, AINU1d
49, Analog Input Universal 2 a, AINU2a
50, Analog Input Universal 2 b, AINU2b
51, Analog Input Universal 2 c, AINU2c
52, Analog Input Universal 2 d, AINU2d
UM353-1B
H
N
3
21
35
34
20
52
April 2012