Example circuits
A.2 Control circuit connection
A.2.8

Connecting the evaluation unit to the analog output

Requirements
3RW52 soft starter with analog output
Evaluation unit for displaying the analog output signal
Parameterized analog output (Page 121)
Procedure
Connect the evaluation unit:
Disconnect the voltage at terminals AQ U+ / AQ-
Result
The actual average phase current of the motor is displayed in % at the evaluation unit via the
analog output.
232
Disconnect the current at terminals AQ I+ / AQ-
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
SIRIUS 3RW52 Soft Starter