Functions

8.8 Test mode

8.8
Test mode
Requirements
3RW52 soft starter from firmware version V2.0
Accessories, e.g. 3RW5 HMI High Feature or 3RW5 PROFINET or
PROFIBUS communication module
Operating principle
For the test mode function "Test with small load" (Page 145), the 3RW52 soft starter must be
in test mode. In test mode, the LED "RN" flashes green on the 3RW52 soft starter. For
normal operation, the 3RW52 must be in Normal operation.
The parameters "Test mode" and "Normal operation" are not available in the
3RW5 HMI High Feature.
Setting options
3RW5 HMI High Feature (firmware version V2.0 or higher)
Access protection to 3RW5 HMI High Feature is not active or has been reset.
Menu: "Parameters > Soft Starter > Additional parameters"
Note
Activating test mode
If you activate or deactivate "Test with small load" on the 3RW5 HMI High Feature, you
will automatically also switch to Test mode or Normal operation. For activation and
deactivation on the 3RW5 HMI High Feature, the 3RW5 HMI High Feature must have
master control.
With SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
Brief overview: Window "Project Navigation" with current project under created
Soft Starter > "Commissioning" > Window "Work area" > "Soft Starter > Functions >
Test mode"
With a fieldbus via a 3RW5 communication module (only via a 3RW5 PROFINET or
PROFIBUS communication module):
– With SIRIUS Soft Starter ES (TIA Portal) Premium / Professional
– Configuration software of the control system (e.g. STEP 7 with corresponding HSP)
– User program
144
Brief overview: See SIRIUS Soft Starter ES (TIA Portal) via the local interface on the
3RW5 HMI High Feature
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005