Parameter
Do control after log off
Messages to show
Operation display
Languages
Only visible if an additional language has been added.
1)
SIRIUS 3RW52 Soft Starter
Equipment Manual, 04/2020, A5E35630451002A/RS-AE/005
Description
This parameter describes the response after logging off while the motor is running.
Continue with motor control
The master control is retained by the 3RW5 HMI High Feature.
Stop motor and give back control (factory setting)
The motor stops and the master control is no longer with the 3RW5 HMI High Feature.
Refer to chapter Operating modes and master control function (Page 32).
If errors and/or warnings are enabled, they will appear as pop-up windows in the display of
the 3RW5 HMI High Feature as soon as they occur.
Errors
Enable (factory setting)
Disable
Warnings
Enable (factory setting)
Disable
You can select up to 5 different measured values from a list of measured values. These
measured values are then shown in the operation display of the 3RW5 HMI High Feature.
You will find further information on measured values in chapter Monitoring the measured
values of the 3RW52 soft starter with the 3RW5 HMI High Feature (Page 154).
Measured value 1: Phase current average (%) (factory setting)
Measured value 2: Phase current average (rms) (factory setting)
Measured value 3: Phase current I L1 (rms) (factory setting)
Measured value 4: Phase current I L2 (rms) (factory setting)
Measured value 5: Phase current I L3 (rms) (factory setting)
The required language is set in the "Languages" menu.
English (factory setting)
German
French
Spanish
Italian
Portuguese
Chinese
Additional language
1)
6.12 Parameterizing the High Feature 3RW5 HMI
(Page 168)
Parameter assignment
125