Panasonic S-160PE1R5B Technical Data & Service Manual page 47

Table of Contents

Advertisement

Type E3
External Static Pressure Setting
Choose one of the methods (selection of "a", "b", "c" within the range of dotted line as shown in the flowchart below)
and make settings.
a. No setting changes:
When using as it is factory preset at shipment.
(If resetting after external static pressure setting once, it might be different from factory preset.)
b. Manual setting (on PCB):
This is static pressure setting excepting factory preset at shipment. Dip switch select method.
c. Manual setting (by timer remote controller):
Static pressure setting excepting factory preset at shipment.
Flow of External Static Pressure
Start of external static pressure setting
Setting of shipment : line 5
Is it designed
and installed at the setting
line at shipment on
PQ line drawing?
See the section
Selection methods
of external static
pressure setting
a. No setting changes
N OTE
(1) See the Tables 1-9-2, 1-9-3 and Fig. 1-9-2 for details on the relationship between the value of item code "5d"
and the external static pressure.
(2) When set in group control (connecting multiple indoor units with one timer remote controller), set each indoor
unit to item code "5d".
When amending the setting after selecting [ b. Manual setting] (due to airflow path changes, etc.), it is
necessary to cancel [b. Manual setting] (switching OFF positions).
When [b. Manual setting] has not been cancelled, [c. Manual setting] will be activated if selected, but [b. Manual
setting] takes precedence when the power is switched back on after power outages, etc.
Make sure the external static pressure is in a range of specifications.
Then proceed the external static pressure setting.
Improper settings can cause noise, a shortage of airflow volume and water
CAUTION
leakage.
See the Fig. 1-9-2 for the external static pressure setting range.
Be sure to set the [External Static Pressure Setting] once again after amending
the airflow path for the duct or air outlet after setting the external static pressure.
No
1-9-4.
Yes
No
b. Manual setting
(Setting on PCB)
Setting switches of TP6 or
TP3 or TP1
See the section "1-9-1. How to
Set on PC Board".
Completion of external static pressure setting
Operating by
timer remote
controller
Yes
Item code 5d : Setting 1, 3, 6
See the section 1-9-2. or 1-9-3.
1-9-2
c. Manual setting
(*Note 1) (*Note 2)
1