4. Mini VRF System Alarm Codes
4 Check the
4-1
situation
4-2
4-3
4-4
4-5
4-6
5 Check
5-1
operation
5-2
5-3
5
5-4
5-5
5-6
6 Check
6-1
history
6-2
7 Check the
7-1
HIC boards
8 Check the
compressor
8-1
8-2
Outdoor air intake temperature is high.
May be caused by poor outdoor unit air flow
(dirty or clogged heat exchanger, blocked discharge port, etc.)
Air short circuit has occurred. This is a phenomenon when
discharged air (exhaust heat) from the outdoor unit is drawn back
into the suction vent.
Indoor air intake temperature is high.
The filter of the indoor unit is clogged.
Air short circuit has occurred. This is a phenomenon when
discharged air (exhaust heat) from the indoor unit is drawn back
into the suction vent.
Possible to operate.
Operating pressure is affected by pressure overload.
Tends to have an overcharge of refrigerant in the system.
Tends to operate for a long time turning gas back into liquid.
Tends to have insufficient refrigerant charge in the system.
Even though the high pressure saturation temperature is 43°C or
less, the secondary current of the inverter is high.
(The frequency (Hz) ends up dropping due to the current.)
Dividing the outdoor EEPROM INV operation time by the number
of times oil was supplied to the system yields 3 hours or less.
There is a history of H31 in the pre-trip counter of the outdoor
EEPROM alarm history.
The results of HIC board IPM Pass/Fail Tests show the outside the
range of the resistance of a conforming part listed in the next page.
The compressor is causing a failure in the insulation.
The winding resistance of the compressor is abnormal.
Standard winding resistance
3-phase model
(6.5HP – 9HP)
U-V : 0.735 ohm
U-W : 0.715 ohm
V-W : 0.715 ohm
HP: horse power
single-phase model
(6.5HP)
U-V : 0.229 ohm
U-W : 0.223 ohm
V-W : 0.223 ohm
5-26
Mini VRF SYSTEM
Trouble Diagnosis
Yes
Take measures.
No
4-2
Yes
Correct
No
4-3
Prevent air short
Yes
circuit.
No
4-4
Yes
Take measures.
No
4-5
Yes
Clean the filter.
No
4-6
Prevent air short
Yes
circuit.
No
5-1
Yes
5-2
No
6-1
Yes
5-3
No
5-4
Adjust the amount
Yes
of refrigerant.
No
5-4
Check the operation
Yes
of functional parts.
No
5-5
Adjust the amount
Yes
of refrigerant.
No
5-6
Replace the
Yes
compressor.
No
See what happens.
Yes
6-2
No
6-2
Replace the
compressor and add
Yes
oil. However, if 6-1
was "no", it is not
necessary to add oil.
No
7-1
Yes
Replace HIC board.
No
8-1
Replace the
Yes
compressor.
No
8-2
Replace the
Yes
compressor.
No
9-1