Panasonic S-160PE1R5B Technical Data & Service Manual page 29

Table of Contents

Advertisement

1-3. Other Component Specifications
Outdoor Units U-160PZH2R5
MODEL No.
Power Transformer
Rated
Source
Secondary
Coil resistance
Thermal cut off temperature
Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4
Resistance
Thermistor (Discharge gas sensor): TH5
Resistance
Relay (Comp. Magnetic Contactor)
Coil rated
Contact rating
Coil resistance (at 20°C)
Sol-Control-Valve
Sol-control-valve
Magnetic coil
4 way valve
4 way valve
Electro magnetic coil
Outdoor Unit
VAC, Hz
kΩ
kΩ
VAC
VAC, A
1-1-1-3-1
U-160PZH2R5
-20°C: 38.48±2%     20°C: 6.517±2%
-10°C: 23.67±2%     30°C: 4.448±2%
0°C: 15.00±2%     40°C: 3.100±2%
5°C: 12.06±2%     45°C: 2.607±2%
10°C: 9.765±2%     50°C: 2.203±2%
60°C: 13.85±2%     
65°C: 11.59±2%     
70°C: 9.743±2%     95°C: 4.367±2%
75°C: 8.228±2%      100°C: 3.764±2%
80°C: 6.981±2%     105°C: 3.256±2%
CAM-BD24MS-1
CAM-MD12MS-206,208,210
SHF-20B-46-DC
SQ-D23015-002283 DC15.4V(898mA)
85°C: 
5.946±2%
90°C: 5.086±2%
1 1 1