Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
Actuator model 500, 1000, 2000
•
•
•
•
•
•
6.2.14
Blinker / Local Selector Configuration
Default configuration for Blinker / Local Selector relay is off (always Open). In Blinker
configuration, during actuator movement the relay changes their status each 500 ms (Motor
Running function). In Local Selector configuration (with Local Interface OM3 installed), the relay
is CLOSE when OM3 switch is on REMOTE, while it is OPEN when OM3 switch is on LOCAL.
To configure Blinker or Local Selector monitoring function (when OM3 is present):
•
•
•
•
•
•
Actuator Configuration
Enter set up configuration: move switch SW3 to position ON (configuration function)
Move switch SW4 to position 9
Move switch SW6 to position 1
Confirm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for confirmation
Exit set up configuration (move switch SW3 to position 1) or proceed with
the next parameter
Enter set up configuration: move switch SW3 to position ON (configuration function)
Move switch SW4 to position 4
Move switch SW6 to position 1 (Blinker) or 2 (Local Selector)
Confirm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for confirmation
Exit set up configuration (move switchSW3 to position 1) or proceed with
the next parameter
Section 6: Actuator Configuration
October 2020
37