Section 6: Actuator Configuration
October 2020
6.2.15
3-WIRES/ 2-WIRES Remote Control Configuration
Remote Control in 3-WIRES configuration works as follow: command on terminal 35 to OPEN,
command on terminal 36 to CLOSE. Remote Control in 2-WIRES configuration works as
follow: command present on terminal 35 to OPEN, command absent on terminal 35 to CLOSE;
terminal 36 not used. As default, remote command parameter is configured as 3-WIRES.
To configure Remote Control parameter:
6.3
Configuration of the Keystone EPI2 by a
PDA / PC and 'A Manager' Software
If one of the optional module OM1, OM9 or OM11 is installed on the Keystone EPI2 and
this card features Bluetooth interface, the actuator configuration can be performed by
means of the 'A Manager' software installed on the PDA or PC.
Only Blinker/ Local Selector relay and heater cannot be configured by means 'A Manager'
software. The relevant Instruction and Operating Manual is available with the
'A Manager' software.
WARNING
!
The controls available via Bluetooth allow full actuator operability at a distance.
Emerson will not accept any responsibility for damages or injuries caused by an improper
use of your Bluetooth PDA.
38
Enter set up configuration: move switch SW3 to position ON (configuration function)
Move switch SW4 to position 9
Move switch SW6 to position 5 (3-WIRES) or 6 (2-WIRES)
Confirm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for confirmation
Exit set up configuration (move switch SW3 to position 1) or proceed with
the next parameter
Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
Actuator Configuration