Close Limit Configuration By Position; Close Limit Configuration; Open Limit Configuration By Position - Emerson Keystone EPI2 63 Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
6.2.2

Close Limit Configuration by Position

Enter set up configuration:
6.2.3

Close Limit Configuration

6.2.4

Open Limit Configuration by Position

Actuator Configuration
Move switch SW4 to position 2
Move switch SW6 to position 1
Move switch SW3 to position ON
Confirm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for confirmation
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
Move switch SW3 to position ON
Drive the actuator to the close position using the handwheel
Move switch SW4 to position 0
Move switch SW6 to position 0
Confirm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for confirmation
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
Move switch SW4 to position 3
Move switch SW6 to position 1
Move switch SW3 to position ON
Confirm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for confirmation
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
Section 6: Actuator Configuration
October 2020
31