Section 6: Actuator Configuration
October 2020
6.2.5
Open Limit Configuration
•
•
•
•
•
•
•
6.2.6
Close Limit Configuration by Torque
•
•
•
•
•
•
•
6.2.7
Open Limit Configuration by Torque
•
•
•
•
•
•
•
32
Move switch SW3 to position ON
Drive the actuator to the open position using the handwheel
Move switch SW4 to position 1
Move switch SW6 to position 0
Confirm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for confirmation
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
Move switch SW4 to position 2
Move switch SW6 to position 0
Move switch SW3 to position ON
Confirm by pushing ENTER pushbutton SW5 (red LED switch on)
Operate the actuator to closing direction by local/remote control and wait until it
stops by torque
When the setting is completed, the red LED switches off
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
Move switch SW4 to position 3
Move switch SW6 to position 0
Move switch SW3 to position ON
Confirm by pushing ENTER pushbutton SW5 (red LED switch on)
Operate the actuator to opening direction by local/remote control and wait until
it stops by torque
When the setting is completed, the red LED switches off
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
Actuator Configuration