Open Limit Configuration; Close Limit Configuration By Torque; Open Limit Configuration By Torque - Emerson Keystone EPI2 63 Installation, Operation And Maintenance Manual

Table of Contents

Advertisement

Section 6: Actuator Configuration
October 2020
6.2.5

Open Limit Configuration

6.2.6

Close Limit Configuration by Torque

6.2.7

Open Limit Configuration by Torque

32
Move switch SW3 to position ON
Drive the actuator to the open position using the handwheel
Move switch SW4 to position 1
Move switch SW6 to position 0
Confirm by pushing ENTER pushbutton SW5
When pushing SW5, the red LED switches on for confirmation
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
Move switch SW4 to position 2
Move switch SW6 to position 0
Move switch SW3 to position ON
Confirm by pushing ENTER pushbutton SW5 (red LED switch on)
Operate the actuator to closing direction by local/remote control and wait until it
stops by torque
When the setting is completed, the red LED switches off
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
Move switch SW4 to position 3
Move switch SW6 to position 0
Move switch SW3 to position ON
Confirm by pushing ENTER pushbutton SW5 (red LED switch on)
Operate the actuator to opening direction by local/remote control and wait until
it stops by torque
When the setting is completed, the red LED switches off
Exit set up configuration, moving switch SW3 to position 1 or proceed with the
next parameter
Installation, Operation and Maintenance Manual