en | Installing the Aspiration smoke detector
5

Installing the Aspiration smoke detector

5.1

General

The regulations, guidelines and provisions described in Regulations apply.
The following must be observed when installing the FCS-320-TM Aspirating Smoke Detector:
Warning!
The equipment may only be installed by authorized and qualified personnel!
!
Switch off the unit before carrying out any connection work!
5.2

Installing the unit

Notice!
When selecting the installation location, ensure that the LEDs are easily visible.
Remember when planning that the unit fans generate a noise level of approx. 40 dB(A).
In order to prevent damage to the device, ensure that the installation location is not in a door
opening area.
Turning the detection module in the cover
In order to turn the detection module in the cover of the FCS-320-TM detection unit by 180°,
proceed as follows:
2020.04 | 2.1 | F.01U.130.928
Do not interfere with, modify or convert the equipment. If adjustments cannot be
avoided, consult with the operator, the unit manufacturer and/or the supply company.
All changes to the house mains (230 V/400 V supply) and to third-party systems must be
executed by the builder. This includes e.g.
Primary connection of the mains charger
Carrying out any potentially essential lightning and surge protection measures in
compliance with relevant standards
Aspiration from above
Ensure that the air outlet of the aspiration smoke detector is not obstructed. Maintain a
distance of at least 10 cm between the air outlet of the FCS-320-TM and the surrounding
objects (e.g. wall).
Aspiration from below
If the air-return pipe is directed upwards, it must be guaranteed that no foreign bodies or
dripping water can penetrate the air return. You should therefore use a short, downward
angled pipe.
Remove the four screws (see figure below for positions).
Now turn the cover and fasten the detection module again with the four screws.