Planning With Single-Hole Monitoring; I-Pipe System - Bosch FCS‑320‑TM Series Operation Manual

Conventional aspiration smoke detector
Hide thumbs Also See for FCS‑320‑TM Series:
Table of Contents

Advertisement

Conventional Aspiration smoke detector
Double U‑pipe system
1 pipe system
FCS-320-TM
FCS-320-TM-R
Double U‑pipe system Air sampling
Ø of air sampling
openings in mm
a
Punch diameter of the aspiration reducing film sheet
4.7

Planning with Single-hole Monitoring

Depending on the pipe configuration, the following system parameters are used to detect a
single air sampling opening or a particular number of obstructed air sampling openings.
Planning is to be carried out according to regulations specified in Standard pipe planning,
page 32 . Additionally, the following limiting values and opening diameters must be observed.
An additional accessory (air filter, condensate separator etc.) can have an effect on the
maximum pipe length.
4.7.1

I-pipe system

1 pipe system
FCS-320-TM
FCS-320-TM-R
Min. distance FCS-320-TM - 1st air sampling opening
Max. distance FCS-320-TM - 1st air sampling opening
Max. total pipe length per pipe system
Max. total pipe length per pipe system for a fan voltage < 10.5 V
Min. distance between 2 air sampling openings (d)
Max. distance between 2 air sampling openings (d)
Max. number of air sampling openings (n) per pipe system
Bosch Sicherheitssysteme GmbH
B
Double U‑pipe system
opening
A
a
B
FAS / FCS
A
I-pipe system for space protection
Pipe Ø 25 mm
Additional pipe Ø 12 mm
Pipe Ø 25 mm
Additional pipe Ø 12 mm
FAS / FCS
A
Number of air sampling openings
4
4.4
-
C
D
B
Operation guide
Planning | en
8
3.0
3.8
E
2 m
20 m
40 m
5 x 3 m
30 m
5 x 3 m
4 m
10 m
5 units
2020.04 | 2.1 | F.01U.130.928