Pipe System - Bosch FCS‑320‑TM Series Operation Manual

Conventional aspiration smoke detector
Hide thumbs Also See for FCS‑320‑TM Series:
Table of Contents

Advertisement

Conventional Aspiration smoke detector
Cable bushings
Dimensions (H x W x D)
Weight
Housing material
Housing color
Environmental conditions
Protection category according to EN 60529
Permissible temperature:range;
Aspiration smoke detector
PVC pipe system
ABS pipe system
Permissible relative humidity (non-
condensing)
Special features
Sound power level (at 9 V fan voltage)
Response sensitivity (light obscuration)
Life cycle of fan (at 12 V and 24 °C)
3.8.2

Pipe system

Maximum pipe length Ø 25 mm
Additional maximum pipe length Ø 12 mm
Maximum number of air sampling openings
Maximum length of aspiration hose per
ceiling lead-through
Maximum size of monitoring area
Bosch Sicherheitssysteme GmbH
Aspiration pipe
Air-return pipe
Housing base sides
Housing base rear wall
Without air return
With pipe section 100 mm/pipe bend
With air return
1 pipe
1 pipe
8 x M 20 and 2 x M 25
4 x M 25
222 x 140 x 70 mm
Approx. 0.8 kg
Plastic (ABS)
Papyrus white (RAL 9018)
IP 20
IP 42
IP 54
-20 °C to +60 °C
-10 °C to +60 °C
-40 °C to +80 °C
Max. 95%
40 dB(A)
0.5 to 2.0%/m
60,000 hrs
50 m
8 x 3 m
8
3 m
²
400 m
Operation guide
Technical specifications | en
2020.04 | 2.1 | F.01U.130.928