Installing The Aspirating Smoke Detector; General; Installing The Unit - Bosch FCS-320-TM Operation Manual

Fcs-320-tm aspirating smoke detector
Hide thumbs Also See for FCS-320-TM:
Table of Contents

Advertisement

FCS-320-TM Aspirating Smoke Detector
4

Installing the Aspirating Smoke Detector

4.1

General

The regulations, guidelines and provisions described in Section 3.1 Regulations, page 31 apply.
The following must be observed when installing the FCS-320-TM Aspirating Smoke Detector:
1.
2.
WARNING!
The equipment may only be installed by authorized and qualified personnel!
Switch off the unit before carrying out any connection work!
4.2

Installing the Unit

NOTICE!
The aspirating smoke detector can be installed with the aspiration device pointing upwards or
downwards. Turn the detector module in the cover by 180° as applicable.
A
Figure 4.1 Installation of the FCS-320-TM
Aspiration from above
Ensure that the air outlet of the aspirating smoke detector is not obstructed. Maintain a
distance of at least 10 cm between the air outlet of the FCS-320-TM and the surrounding
objects (e.g. wall).
Bosch Sicherheitssysteme GmbH
Do not interfere with, modify or convert the equipment. If adjustments cannot be
avoided, consult with the operator, the unit manufacturer and/or the supply company.
All changes to the house mains (230 V/400 V supply) and to third-party systems must be
executed by the builder. This includes e.g.
Primary connection of the mains charger
Carrying out any potentially essential lightning and surge protection measures in
compliance with relevant standards
When selecting the installation location, ensure that the unit displays are easily visible.
Remember when planning that the unit fans generate a noise level of approx. 40 dB(A).
In order to prevent damage to the device, ensure that the installation location is not in a
door opening area.
1
≥ 10 cm
Operation Guide
Installing the Aspirating Smoke Detector | en
B
2
1
A
Aspiration device
upwards
≥ 10 cm
B
Aspiration device
downwards with air outlet
opening upwards
1
Smoke aspiration pipe
2
Air-return Pipe
F.01U.130.928 | 1.0 | 2009.11
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fcs-320-tm-r

Table of Contents