Conventional Aspiration smoke detector
8.
8

Maintenance

8.1

Visual check

Check whether...
8.2

Detection Module and Alarm Transfer

Proceed in accordance with Checking the Detection Module and Alarm Transfer, page 74 . Also
check the detection module visually for exterior contamination or damage and replace it if
necessary.
Notice!
A hardware defect in the detection module is displayed in the "Fault messages" screen of the
diagnostic software.
8.3

Pipe System

Check the pipe system and the air sampling openings for obstruction in areas susceptible to
dust particles or icing. If necessary, blow out the pipe system and air sampling openings with
blast air. Use a mobile cylinder of compressed air (blowing-out system) or activate the manual
blowing-out system located on site. The components (compressors, compressed air
containers, dryers) required to supply the compressed air can be obtained directly from the
relevant compressed air system suppliers.
Caution!
Before blowing out the pipe system, disconnect the FCS-320-TM from the pipe system;
!
otherwise, the airflow sensor will be damaged.
Bosch Sicherheitssysteme GmbH
Once the preselection time has expired, switch the FCS-320-TM-R to aspiration. The
smoke must now be available at the selected aspiration point. The smoke level will
display if smoke is detected by the FCS-320-TM-R. The display of the selected aspiration
point turns green and the determined time is entered. Teaching mode for the selected
aspiration point is exited.
The pipe system is securely installed and undamaged (where freely accessible)
The air sampling openings of the pipe system are free
The aspiration pipe and connection cable are securely connected
The FCS-320-TM is undamaged.