en | Commissioning
Checking the pipe system connection
1.
2.
3.
4.
2020.04 | 2.1 | F.01U.130.928
Connect the test pipe.
Connect the pressure measuring hose to the adapter connection B. When carrying out a
limited functional test without a digital precision pressure gauge, the connection for the
pressure measuring hose on the test pipe must be closed.
Connect the 4-pin plug of the adapter to the digital pressure gauge.
Connect the PC to the FCS-320-TM through the diagnostic appliance and start the
diagnosis program.
Operation guide
Conventional Aspiration smoke detector
1
Test pipe
2
Aspiration borings
3
Pressure measuring hose
4
Adapter
5
Digital precision pressure
gauge
A/B Adapter connection
Bosch Sicherheitssysteme GmbH