Advertisement

Conventional Aspiration smoke detector
5.6

Data logging

Connecting a PC to the FCS-320-TM
The FAS‑ASD‑DIAG Diagnostic Software is used to conduct the device tests.
The current airflow sensor data, smoke level values, various status values and the parameters
configured via the programming software can be read out locally using a laptop. This makes it
much easier to detect altered operation conditions in the event of service being carried out.
The data is read out via the infrared port of the FCS-320-TM to the diagnostic appliance. The
diagnostic appliance can be secured to the aspirating smoke detector with a unit mounting or
be kept in a straight line (± 10°) with the infrared port at a distance of up to 3 m. The supplied
USB cable connects the diagnostic appliance to the USB port of the PC/laptop (see figure
above).
The data that is read out is stored in the appliance for 72 hours for diagnostic purposes.
Notice!
For correct color display, the monitor used and the graphics card must be able to display
more than 256 colors.
6

Installation of the pipe system

At the very least, the pipes and fittings used for the pipe system must comply with class 1131
according to EN 61386‑1, 2004. Class 1131 requires the following of the pipe system in use:
Features
Compression resistance
Shock resistance
Temperature range
The pipe system must be constructed using the following pipes and the associated fittings:
Smoke aspiration
pipe
* PVC pipes do not correspond to the temperature range given above.
Notice!
When constructing the pipe system, observe the temperature range specified in Pipe system,
page 25 .
Bosch Sicherheitssysteme GmbH
3
4
Exterior diameter
25 mm
Operation guide
Installation of the pipe system | en
2
Severity
125 N
0.5 kg, drop height of 100 mm
-15 °C to +60 °C
Internal diameter
ABS
21.4 mm
1 FAS‑ASD‑DIAG
1
2 Infrared port
3 USB connection
cable
4 USB port
PVC*
21.2 mm
2020.04 | 2.1 | F.01U.130.928
63