en | Commissioning
3.
4.
5.
6.
7.
Notice!
On completion of the functional tests, the original settings must be restored.
The commissioning of the device with the pipe system must be repeated from Calibrating the
Airflow Sensor, page 73 .
Once commissioning has been concluded, the set values must be collected and saved using
the FAS‑ASD‑DIAG Diagnostic Software. A printout of the set values should be placed in the
project folder.
7.8

Fire Source Identification Commissioning

Fire source identification is set using the FAS‑ASD‑DIAG Diagnostic Software via the
"ROOM·IDENT" screen.
1.
Notice!
The commissioning of the fire source identification does not make any distinction between
the "ROOM·IDENT" function and the "Fire alarm after ROOM IDENT" function.
2.
3.
4.
5.
6.
7.
2020.04 | 2.1 | F.01U.130.928
After initialization, close the 4.2 mm aspiration boring of the test pipe with some duct
tape. After approximately 5 secs, the fault indication on the device must start to flash.
After approximately 35 secs, the fault indication on the device must be permanently
illuminated. The device reports the malfunction "Air flow too low (static evaluation)". The
airflow value is approximately ‑35%.
Open the 4.2 mm aspiration boring again. After a few seconds, the fault indication on the
FCS-320-TM must stop flashing.
Open the 7.0 mm aspiration boring on the test pipe. After approximately 5 secs, the fault
indication on the device must start to flash. After approximately 35 secs, the fault
indication on the device must be permanently illuminated. The device reports the
malfunction "Air flow too high (static evaluation)". The airflow value is
approximately +85%.
Close the 7.0 mm aspiration boring again. After a few seconds, the fault indication on the
FCS-320-TM must stop flashing.
Remove the test pipe and reconnect the pipe system.
Click the [Train] button. This opens the view with adjustable values used to determine
the transport times for fire source identification in areas A-E.
First enter the number of air sampling openings.
Then enter the blowing out time and voltage of the blowing out and aspiration fan.
You can access the Help function by clicking the question mark to the right of the relevant
setting.
Click the appropriate aspiration point (A-E) for which the transport time is to be
determined.
Enter the preselection time necessary to reach the aspiration point and supply the smoke.
Once the selected preselection time has expired, the appropriate smoke aspiration point
must be charged with smoke. Once the preselection time has expired, the smoke must be
available at the aspiration point for another 10 to 15 seconds.
Using the smoke level, check that there is no smoke in the aspiration pipe.
Click the [Start] button. The FCS-320-TM-R switches to the aspiration pipe blowing out.
The display of the aspiration point concerned is yellow.
Operation guide
Conventional Aspiration smoke detector